Customization: | Available |
---|---|
Breaking Capacity: | High Voltage Circuit Breakers |
Operation: | Energy-storage Type |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
NO |
Item |
Unit |
Value |
||
1 |
Rated voltage |
KV |
40.5 |
||
2 |
Rated insulation level |
Power frequency withstand voltage |
Dry test |
95 |
|
Wet test |
80 |
||||
Lightning impulse withstand voltage (peak) |
185 |
||||
3 |
Rated current |
A |
1250,1600,2000 |
||
4 |
Rated short-circuit breaking current |
KA |
20,25,31.5 |
||
5 |
Rated operation sequence |
|
0-0.3s-combination-180s-combination |
||
6 |
Rated short circuit current breaking times |
times |
12 |
||
7 |
Rated short circuit closing current (peak) |
KA |
50,63,80 |
||
8 |
Rated peak withstand current |
||||
9 |
Rated short-time withstand current |
KA |
20,25,31.5 |
||
10 |
Rated short circuit continuous current |
S |
4 |
||
11 |
Average opening speed |
m/s |
1.5±0.2 |
||
12 |
Average closing speed |
0.7±0.2 |
|||
13 |
Contact closing bounce time |
s |
≤2 |
||
14 |
Three-phase combined (minute) gate synchronous time difference |
≤2 |
|||
15 |
Closing time |
≤150 |
|||
16 |
Opening time |
≤60 |
|||
17 |
Mechanical life |
times |
10000 |
||
18 |
Rated operating voltage and auxiliary circuit rated voltage |
V |
DC220,110,24 |
||
AC220,110,24 |